Ground Rod Calculator: Earthing, Lightning and Shock Safety

Free ground rod calculator and earthing simulator: find a rod's resistance for your soil, how many rods you need, why a rod does not trip a breaker, lightning step and touch voltages, static discharge time, and the grounding rules for the US, Canada, UK, Australia, Europe and Vietnam.

Show:

How it all fits together

Drag to move · Ctrl/⌘ + scroll or pinch to zoom · double-click to zoom in
A house wired to the utility transformer, with its ground rods in the soil Utilitytransformer Utility earth≈ 20 Ω hot (live)neutral Meter Panel N–G bond(neutral tied to ground) House rod circuit wiresground wire (EGC) Metalcase rod at theappliance only the soil between the two earths voltage rings in the soil

Not sure of your soil? Pick the nearest type; the soil is the biggest unknown. A rod's resistance to earth varies a lot with moisture, frost and season, so measure it (fall-of-potential test) rather than trusting any calculation.

Resistance to earth
–
A single rod would be
–
Rods needed for the target
–

Longer rod or more rods?

What a ground rod does, and what it doesn't

  • It ties your wiring to the earth's potential, so the whole system can't float to a dangerous voltage compared with the ground you stand on (a nearby lightning strike, a utility line touching a primary line, static build-up).
  • It does not make breakers trip. Even a perfect rod is in series with the utility's own earth, so a hot-to-case fault through earth is only a few amps. Tab 2 shows this. The thing that trips the breaker is the grounding wire (EGC) and the neutral bond at the panel, which give the fault a metal road back to the transformer.
  • It cannot "absorb" a lightning strike. A strike carries tens of thousands of amps; the rod's job is to be one part of a bonded system so everything rises together. Tab 3.
  • It does little for carpet shocks. Static is drained by humidity and surfaces long before the house earth matters. Tab 4.

Ground rods, earthing and electrical safety explained

A ground rod (earth electrode) is a metal rod driven into the soil and wired to your electrical panel. Its resistance to earth is set mostly by the soil, then by the rod's length and the number of rods. This tool calculates it, shows what a rod does and does not do in a shock fault, models the voltages in the ground around a lightning strike, checks static discharge time, and summarises the main rules by region.

Common questions

  • How deep should a ground rod be? In the US an 8 ft (2.4 m) rod fully in contact with the soil; in Canada rods are typically 3 m (10 ft); in Australia at least 1.2 m. Longer rods help more than fatter ones because the current reaches deeper, often wetter soil.
  • Why two ground rods? In the US, one rod must be supplemented by another electrode unless it measures 25 Ω or less, and rods must be at least 6 ft apart so they don't share the same patch of soil. Compare 1 and 2 rods in tab 1.
  • Does the ground rod trip the breaker? No. Tab 2 shows the fault current through a rod is only a few amps; the grounding wire to the panel and the neutral-ground bond clear faults.
  • Does a ground rod protect from lightning? It is one part of a bonded system. It does not conduct a strike harmlessly; tab 3 shows the voltages.
  • What resistance should a ground rod have? It depends on the system and country: 25 Ω is the US benchmark for a single rod; TT systems use RA × IΔn ≤ 50 V; many practical designs aim for much less. Tab 5 lists the main rules.